Extracted from Jul/1998 issue of Can/Am EMTP News Frequency Scans and Harmonics Gabor Furst revealed to the general public the existence of HARMONIC FREQUENCY SCAN ( HFS) using public E-mail of the Fargo list server. This was just prior to release of the April newsletter, in a message dated April 19 th. The announcement had "Subject: HFS - Harmonic Frequency Scan." Prior to a detailed summary, author Furst provided the following introduction: "Harmonic Frequency Scan (HFS) is the new ATP Request for performing harmonic analysis. HFS is a companion procedure to Frequency Scan (FS). FS performs a series of phasor solutions using user specified 14 type sources, by incrementing the source frequencies in a linear or logarithmic fashion. The amplitude of the sources is kept constant. HFS on the other hand, performs a set of phasor solutions on sources entered by the user, but does not change either the amplitude or angle of these sources, nor does it increment their frequencies. HFS therefore is a procedure which is identical with the methods used in all commercial harmonic analysis software known to the writer. This option is available in TPBIG versions.... Power quality has become a major preoccupation of transmission planners in the last decade and its importance is increasing with the proliferation of power electronics applications in the various industries and in the homes. Harmonic analysis is perhaps the most important branch of power quality studies. Harmonic analysis with ATP has previously been performed in the time domain. While this is a perfectly legitimate approach and in some ways even superior to the generally used approach for harmonic analysis, it has a number of drawbacks. These are discussed in the HFS Report to be placed in the Fargo Server archives shortly. HFS features will be described in the Server report referred to above. The following is a brief summary... "