12. Super conducting transformers
12.6 Conceptual design
Some conceptual designs are tabled as follows. Expecting future great development in technology, it will be still difficult to be competitive.
Table 12.1 Super conducting transformer conceptional designs
| Type |
Conventional |
SpCon |
SpCon |
SpCon |
SpCon |
| Media |
Oil |
Lq.He |
Lq.He |
Lq.He |
Lq.N2 |
| Rated voltage kV |
500/154 |
500/154 |
500/154 |
500/154 |
500/154 |
| Rated capacity MVA |
1000 |
2000 |
2000 |
2000 |
2000 |
| Impedance % |
20 |
20 |
20 |
20 |
20 |
| Quench in S.C. |
No |
Yes |
No |
No |
No |
| Tech. level |
Present |
Present |
Present |
Future |
Future |
| Losses kW |
| Winding |
4180 |
7.8 |
36.0 |
3.6 |
65 |
| Others |
350 |
700 |
650 |
650 |
670 |
| Iron |
720 |
1080 |
1290 |
1290 |
1080 |
| Penetrate |
-- |
2.0 |
4.0 |
2.0 |
1.5 |
| Refrigerator |
| output |
-- |
9.8 |
40.0 |
5.6 |
66.5 |
| input |
150 |
7000 |
27000 |
2100 |
880 |
| Total |
5400 |
8780 |
28940 |
4040 |
2700 |
| Area % |
| Main body |
100 |
113 |
147 |
147 |
140 |
| Refrigerator |
-- |
1600 |
4370 |
479 |
128 |
| Total |
100 |
1713 |
4517 |
626 |
268 |
| Cost % |
| Main body |
100 |
315 |
1395 |
355 |
330 |
| Refrigerator |
-- |
190 |
440 |
70 |
15 |
| Total |
100 |
505 |
1835 |
425 |
345 |
This page is based on Prof. E.Haginomori's lectures
in Tokyo Institute of Technology, and edited by Japanese ATP User Group.
Copyright (C) Eiichi Haginomori and Japanese ATP User Group.